Current R-454B models use MVP outdoor units and matching MVP multi-position air handlers. The outdoor and indoor requirements are different rows.
Shop VersaPro 2nd GenBeat the Heat and Save Big on MRCOOL DIY Air Conditioning Systems
Save Thousands on Installation with MRCOOL DIY Systems
🏆 Top 10 Authorized MRCOOL Dealer in the USA
USA's Most Trusted MRCOOL Dealer – Free Shipping On Systems*
USA's Most Trusted MRCOOL Dealer – Free Shipping On Systems*
A central ducted heat-pump system can have separate requirements for the outdoor unit, indoor air handler, and optional electric heat kit. Tonnage alone does not determine the circuit.
Technical review: August 2026 • Current R-454B familiesWhat this means for you: the outdoor unit and indoor equipment are not one appliance on one assumed breaker. The installed heat kit can materially change indoor electrical planning.
Read the complete condenser, air-handler, and heat-kit model numbers.
Check voltage, frequency, phase, and the selected indoor-voltage configuration.
Start conductor-ampacity planning from the published MCA for each circuit.
Do not exceed the manufacturer's maximum fuse, MOP, or MOCP value.
Current R-454B models use MVP outdoor units and matching MVP multi-position air handlers. The outdoor and indoor requirements are different rows.
Shop VersaPro 2nd GenCold-climate CENTRAL outdoor models are paired in the current brochure with MVP multi-position air handlers. Match both exact models.
Shop Hyper Heat 2nd GenThe current R-454B catalog family uses UHP outdoor units, UAH air handlers, and UHK heat kits. Do not mix these with legacy MDUO/MDUI data.
Shop Universal 2nd GenPlain English: Minimum Circuit Ampacity tells you how much current the circuit conductors must be capable of safely carrying.
Technical: MCA establishes the minimum required conductor ampacity for the equipment circuit, subject to conductor type, temperature ratings, installation conditions, code, and the authority having jurisdiction.
Plain English: This is the largest protective-device rating the manufacturer publishes for that equipment or circuit.
Technical: Maximum overcurrent protection limits the fuse or circuit-breaker rating. The brochures below use Max Fuse; the heat-kit manuals use MOP. This guide keeps those source labels instead of inventing a “recommended breaker.”
25A and 45A are legitimate standard protective-device ratings. Both appear in current MRCOOL data: VersaPro 30K publishes a 25A outdoor maximum fuse, while the reviewed 8kW heat kits publish a 45A MOP at 230V. Do not replace a published 25A maximum with 30A merely because 30A feels more familiar.
Technical context: NFPA 70 Section 240.6(A) lists 25A and 45A among standard ampere ratings. The exact MRCOOL nameplate and model documentation still control the equipment maximum.
All listed outdoor units are published as 208/230V, 60Hz, single phase. Matching air handlers are published as 115/208/230V, 60Hz, single phase. The indoor MCA column shows 115V / 208–230V in that order.
| Nominal class | Outdoor model | Outdoor MCA | Outdoor max fuse | Indoor model | Indoor MCA 115V / 208–230V | Indoor max fuse | Compatible MVPHK models |
|---|---|---|---|---|---|---|---|
| 18K | MVP-18-HP-C-230A00-O | 16A | 20A | MVP-18-HP-MUAH-230A00-O | 5.5A / 4A | 15A | 05, 08, 10 |
| 24K | MVP-24-HP-C-230A00-O | 19A | 20A | MVP-24-HP-MUAH-230A00-O | 5.5A / 4A | 15A | 05, 08, 10, 15 |
| 30K | MVP-30-HP-C-230A00-O | 22.5A | 25A | MVP-30-HP-MUAH-230A00-O | 8A / 6A | 15A | 05, 08, 10, 15 |
| 36K | MVP-36-HP-C-230A00-O | 24A | 30A | MVP-36-HP-MUAH-230A00-O | 8A / 6A | 15A | 05, 08, 10, 15, 20 |
| 48K | MVP-48-HP-C-230A00-O | 36A | 40A | MVP-48-HP-MUAH-230A00-O | 14.5A / 11A | 15A | 08, 10, 15, 20 |
| 60K* | MVP-60-HP-C-230A00-O | 39A | 40A | MVP-60-HP-MUAH-230A00-O | 14.5A / 11A | 15A | 10, 15, 20 |
Sources: VersaPro 2nd Gen brochure, page 4; air-handler compatibility confirmed in the current shared air-handler service manual, page 40. *The 60K model class has a published cooling capacity of 54,000 Btu/h in the brochure.
All listed outdoor units are published as 208/230V, 60Hz, single phase. Matching air handlers are published as 115/208/230V, 60Hz, single phase. The indoor MCA column shows 115V / 208–230V.
| Nominal class | Outdoor model | Outdoor MCA | Outdoor max fuse | Indoor model | Indoor MCA 115V / 208–230V | Indoor max fuse | Compatible MVPHK models |
|---|---|---|---|---|---|---|---|
| 24K | CENTRAL-24-HP-C-230B00-O | 19A | 20A | MVP-24-HP-MUAH-230A00-O | 5.5A / 4A | 15A | 05, 08, 10, 15 |
| 30K | CENTRAL-30-HP-C-230B00-O | 29.5A | 30A | MVP-30-HP-MUAH-230A00-O | 8A / 6A | 15A | 05, 08, 10, 15 |
| 36K | CENTRAL-36-HP-C-230B00-O | 29A | 30A | MVP-36-HP-MUAH-230A00-O | 8A / 6A | 15A | 05, 08, 10, 15, 20 |
| 48K | CENTRAL-48-HP-C-230B00-O | 38A | 40A | MVP-48-HP-MUAH-230A00-O | 14.5A / 11A | 15A | 08, 10, 15, 20 |
| 60K* | CENTRAL-60-HP-C-230B00-O | 40A | 40A | MVP-60-HP-MUAH-230A00-O | 14.5A / 11A | 15A | 10, 15, 20 |
Source: Hyper Heat 2nd Gen brochure, page 4. *The 60K model class has a published cooling capacity of 54,000 Btu/h.
The current R-454B Universal family uses UHP18 outdoor models and UAH18 air handlers. Outdoor supply is 208/230V, 60Hz, single phase; indoor supply is 115/208/230V, 60Hz, single phase. Indoor MCA is 115V / 208–230V.
| Nominal class | Outdoor model | Outdoor MCA | Outdoor max fuse | Indoor model | Indoor MCA 115V / 208–230V | Indoor max fuse | Compatible UHK models |
|---|---|---|---|---|---|---|---|
| 24K | UHP18024-O | 19A | 20A | UAH18024-O | 5.5A / 3.5A | 15A | UHK05, 08, 10, 15 |
| 30K | UHP18030-O | 29.5A | 30A | UAH18030-O | 8A / 6A | 15A | UHK05, 08, 10, 15 |
| 36K | UHP18036-O | 29A | 30A | UAH18036-O | 8A / 6A | 15A | UHK05, 08, 10, 15, 20 |
| 48K | UHP18048-O | 38A | 40A | UAH18048-O | 14.5A / 10A | 15A | UHK08, 10, 15, 20 |
| 60K* | UHP18060-O | 40A | 40A | UAH18060-O | 14.5A / 10A | 15A | UHK10, 15, 20 |
Source: current Universal R-454B brochure, page 4. *The 60K model class has a published cooling capacity of 54,000 Btu/h.
Plain English: the indoor unit by itself can have a relatively modest electrical requirement. It still has a distinct published supply, MCA, and maximum fuse.
Plain English: electric resistance heat can become the largest electrical load in the HVAC combination. The heat-kit rows must be planned in addition to the outdoor and base air-handler data.
This example demonstrates component relationships; it is not a whole-house service calculation and does not prove that a panel or service upgrade is required.
The condenser's published MCA and maximum fuse describe the outdoor equipment circuit.
The optional heater has its own published 208/230V MCA and MOP values and may use two circuits.
What this means for you: condenser data is not enough to plan auxiliary heat. Confirm the exact air-handler/kit compatibility and the heat-kit wiring diagram supplied with the kit.
| Heat kit | kW | Circuit breakers | Circuit 1 MCA | Circuit 1 MOP | Circuit 2 MCA | Circuit 2 MOP |
|---|---|---|---|---|---|---|
| MVPHK05 / UHK05 | 5 | 1 | 23A / 27A | 25A / 30A | — | — |
| MVPHK08 / UHK08 | 8 | 1 | 37A / 42A | 40A / 45A | — | — |
| MVPHK10 / UHK10 | 10 | 1 | 46A / 53A | 50A / 60A | — | — |
| MVPHK15 / UHK15 | 15 | 2 | 23A / 27A | 25A / 30A | 46A / 53A | 50A / 60A |
| MVPHK20 / UHK20 | 20 | 2 | 46A / 53A | 50A / 60A | 46A / 53A | 50A / 60A |
Sources: current MVPHK and UHK heat-kit installation manuals. The same electrical values are published for the corresponding MVPHK and UHK sizes, but compatibility remains family- and air-handler-specific.
Use MVPHK model compatibility for the exact MVP air handler.
View current MVPHK optionsUse UHK compatibility for the exact current UHP/UAH combination.
View current UHK optionsEquipment-circuit data does not calculate a home's total electrical service. A load calculation considers the panel, service, and other household loads.
Plain English: the 25A outdoor maximum does not describe the indoor unit or either auxiliary-heat circuit.
Technical: MVPHK15 Circuit 1 is MCA 23/27A with MOP 25/30A; Circuit 2 is MCA 46/53A with MOP 50/60A at 208/230V.
Plain English: a 24K label does not collapse this combination into one breaker number.
Technical: MVPHK15 Circuit 1 is MCA 23/27A with MOP 25/30A; Circuit 2 is MCA 46/53A with MOP 50/60A at 208/230V.
Plain English: optional resistance heat can dominate indoor electrical planning.
Technical: UHK20 publishes two equal circuits; each is MCA 46/53A and MOP 50/60A at 208/230V.
Two governed examples: the VersaPro 30K outdoor model publishes a 25A maximum fuse while optional MVPHK15 publishes two separate heat circuits. Universal 36K publishes a 30A outdoor maximum fuse, while optional UHK20 publishes two equal heat circuits. Those are component-specific values, not one whole-system breaker.
What this means for you: send photos of the full nameplates and the exact model documentation. Nominal capacity is useful for identifying the system family, but it cannot answer the circuit question by itself.
Common in some buildings served from a three-phase distribution system. The listed equipment publishes 208/230V support.
The manufacturer's utilization-voltage rating for the equipment.
The familiar residential supply-system term. It is not permission to ignore the nameplate range or selected indoor configuration.
Power the outdoor heat pump, air handler, and installed resistance-heat circuits. These circuits are governed by supply, MCA, and maximum protection.
Carry 24V control signals that tell the equipment when and how to operate.
This distinction is not a universal point-to-point thermostat diagram. Use the diagrams supplied for the exact matched equipment.
Answers: “What supply, conductor ampacity, and maximum protection does this exact HVAC component or heat circuit require?”
Answers: “Can the panel and service support the HVAC system together with all other calculated household loads?”
Current MRCOOL manuals require approved disconnection in fixed wiring and direct the installer to select a service disconnect under applicable local, regional, and national codes. The reviewed manuals also call for an individual branch circuit and recommend an external surge suppressor at the outdoor disconnect.
The reviewed heat-kit manuals specify copper conductors, reference 75°C copper conductor conditions, and call for 2% voltage-drop planning when the branch-circuit length exceeds 100 feet. These are documented installation constraints, not an arbitrary conductor-size prescription. Use the current manual, listed terminations, actual route, ambient conditions, bundling/derating requirements, and the authority having jurisdiction.
There is no family-wide count. The outdoor unit has its circuit requirements, the air handler has its configuration, and the reviewed heat kits add one or two heat circuits depending on the exact kit. Follow the matched wiring diagrams.
The reviewed MRCOOL manuals call for the unit to be connected to an individual branch circuit. Final circuit and disconnect design must follow the exact model, nameplate, current manual, and applicable code.
The air handler has electrical characteristics separate from the outdoor unit. The exact indoor supply and installed heat-kit wiring arrangement determine the final indoor circuit configuration.
Do not assume it does. The table's air-handler values describe the base air handler, while the optional heat-kit manual publishes separate heat-circuit MCA and MOP values.
In the reviewed MVPHK and UHK manuals, those kits divide resistance heat across two separately protected circuits. Each circuit has its own published heater amps, MCA, and MOP.
No. The condenser's maximum fuse applies to the outdoor equipment row. It does not replace the air-handler or heat-kit requirements.
The base air-handler row describes the blower and control equipment. Optional electric resistance heat is a distinct, much larger load with its own published circuit data.
No. The tables contain model-specific differences, and tonnage does not identify the indoor-voltage configuration or installed heat kit. Use complete model numbers.
Yes. They are standard protective-device ratings and appear in current MRCOOL data. Use the exact published maximum; do not round to a more familiar size.
Yes, it can materially change indoor electrical planning. The reviewed 5kW, 8kW, and 10kW kits use one heat circuit; the reviewed 15kW and 20kW kits use two.
No. Heat kits can be significant loads, but a whole-home load calculation must also consider the existing panel, service, and other household loads.
No. Thermostat conductors carry low-voltage control signals. Separate line-voltage circuits power the outdoor equipment, air handler, and heat circuits.
Do not infer a neutral requirement from “115/208/230V” wording alone. The selected indoor-voltage configuration, exact nameplate, supplied wiring diagram, installed accessories, and applicable code control the conductor arrangement.
Send the full outdoor, air-handler, and heat-kit model numbers; clear nameplate photos; the current matching manuals; and the model-specific MCA and maximum-protection tables.
The exact equipment and heat-kit nameplates, the latest matching MRCOOL installation documents, applicable code, and the authority having jurisdiction control the installation. This page is a model-specific planning and lookup resource.
Planning reference: specifications can change. Verify the exact equipment nameplate and latest MRCOOL documentation before installation. Electrical work must follow applicable requirements and be performed by the qualified person responsible for the installation.