Packaged heat pump
The refrigeration circuit heats and cools. Supported models may accept electric resistance heat for auxiliary or emergency operation.
Beat the Heat and Save Big on MRCOOL DIY Air Conditioning Systems
Save Thousands on Installation with MRCOOL DIY Systems
🏆 Top 10 Authorized MRCOOL Dealer in the USA
USA's Most Trusted MRCOOL Dealer – Free Shipping On Systems*
USA's Most Trusted MRCOOL Dealer – Free Shipping On Systems*
One outdoor cabinet can contain the compressor, fans, blower, controls, and either heat-pump components or gas-heating equipment. Optional electric auxiliary heat can add a much larger, separate electrical load.
Technical review: August 2026 • Current catalog + governed MRCOOL documentsThe refrigeration circuit heats and cools. Supported models may accept electric resistance heat for auxiliary or emergency operation.
Gas provides primary heat, while electricity operates the compressor, outdoor fan, supply blower, ignition/control system, and documented gas-section support loads.
What this means for you: the cabinets may look similar, but their heating architecture and electrical planning are not interchangeable.
Technical: published MCA and MOP account for the equipment configuration evaluated by the manufacturer. They are not obtained by adding catalog amp ratings or by guessing from nominal capacity.
Heating: compressor-driven refrigeration cycle.
Optional: compatible electric auxiliary heat.
Electrical implication: the auxiliary heater can materially increase demand and may introduce a separate heat circuit arrangement.
Heating: gas combustion.
Electrical support: blower, controls, ignition, safeties, documented inducer functions, plus the cooling compressor and fan.
Electrical implication: gas supplies the heat energy; electricity still runs the machinery and controls.
Plain English: gas makes the heat, but electricity moves the air, starts and supervises combustion, and powers the air-conditioning side.
Professional detail: the reviewed gas-package documents identify electrical compressor, outdoor-fan, indoor-blower, ignition/control, and gas-heating support functions. Exact components and control sequence remain model-specific. A gas/electric package unit does not have the same resistance-heat demand as an electric heat kit.
Horizontal R-454B models with published base-unit MCA/MOP and compatible 5, 7.5, 10, 15, and 20kW heat-kit options by capacity.
Shop packaged unitsHorizontal/downflow gas package units with published cooling capacity, gas input/output, MCA, and MOP.
Shop gas package unitsCurrent live R-32 inverter models use the MDPH180...D model pattern and support documented 6, 9, and 12kW kit models.
Shop Universal package unitsPlain English: Minimum Circuit Ampacity tells the electrician how much current the circuit wiring must be able to safely carry.
Technical: MCA is the manufacturer-published minimum conductor ampacity for that equipment or heater circuit, subject to conductor type, temperature ratings, installation conditions, code, and the authority having jurisdiction.
Plain English: This is the largest protective-device rating the manufacturer permits for the listed equipment or circuit.
Technical: Source documents use MOP, maximum overcurrent protection, or maximum fuse/breaker. This page preserves the source meaning and does not invent a preferred breaker size.
| Capacity | Model | Cooling | Supply | MCA | MOP | Compatible auxiliary heat |
|---|---|---|---|---|---|---|
| 2 ton | MPH241HO13C | 22,800 Btu/h | 208/230V, 1 phase, 60Hz | 17.9A | 25A | MHK05PC / MHK07PC / MHK10PC |
| 2.5 ton | MPH301HO13C | 28,200 Btu/h | 208/230V, 1 phase, 60Hz | 24.4A | 30A | MHK05PC / MHK07PC / MHK10PC / MHK15PC |
| 3 ton | MPH361HO13C | 34,200 Btu/h | 208/230V, 1 phase, 60Hz | 27.1A | 35A | MHK05PC / MHK07PC / MHK10PC / MHK15PC |
| 3.5 ton | MPH421HO13C | 40,500 Btu/h | 208/230V, 1 phase, 60Hz | 29.9A | 40A | MHK05PC / MHK07PC / MHK10PC / MHK15PC / MHK20PC |
| 4 ton | MPH481HO13C | 46,500 Btu/h | 208/230V, 1 phase, 60Hz | 36A | 45A | MHK05PC / MHK07PC / MHK10PC / MHK15PC / MHK20PC |
| 5 ton | MPH601HO13C | 56,500 Btu/h | 208/230V, 1 phase, 60Hz | 48.6A | 60A | MHK05PC / MHK07PC / MHK10PC / MHK15PC / MHK20PC |
Plain English: MCA rises from 17.9A on the 2-ton model to 48.6A on the 5-ton model. The MOP is not a tonnage lookup; each complete model has its own published value.
Source: VersaPro R-454B Packaged Heat Pump Specifications, pages 3, 4, 6.
| Capacity | Model | Cooling | Supply | MCA | MOP | Gas input / output |
|---|---|---|---|---|---|---|
| 2 ton | MPG24S060MO13C | 22,800 Btu/h | 208/230V, 1 phase, 60Hz | 18.8A | 25A | 60,000 / 48,000 |
| 2.5 ton | MPG30S060MO13C | 28,400 Btu/h | 208/230V, 1 phase, 60Hz | 21.5A | 30A | 60,000 / 48,000 |
| 3 ton | MPG36S090MO13C | 34,000 Btu/h | 208/230V, 1 phase, 60Hz | 25.2A | 40A | 90,000 / 72,000 |
| 3.5 ton | MPG42S090MO13C | 40,000 Btu/h | 208/230V, 1 phase, 60Hz | 29.9A | 45A | 90,000 / 72,000 |
| 4 ton | MPG48S090MO13C | 47,000 Btu/h | 208/230V, 1 phase, 60Hz | 36.4A | 50A | 90,000 / 72,000 |
| 5 ton | MPG60S110MO13C | 57,000 Btu/h | 208/230V, 1 phase, 60Hz | 41.4A | 60A | 110,000 / 88,000 |
Plain English: gas provides heating energy, but these units still publish MCA and MOP because the compressor, fans, blower, and controls require electrical power.
Source: VersaPro R-454B Gas Package Unit Specifications, pages 3, 4.
| Capacity | Model | Cooling | Supply | MCA | MOP | Compatible auxiliary heat |
|---|---|---|---|---|---|---|
| 3 ton | MDPH18036D | 34,000 Btu/h | 208/230V, 1 phase, 60Hz | 35A | 40A | MDPHK06D / MDPHK09D / MDPHK12D |
| 4 ton | MDPH18048D | 47,000 Btu/h | 208/230V, 1 phase, 60Hz | 39.1A | 45A | MDPHK06D / MDPHK09D / MDPHK12D |
| 5 ton | MDPH18060D | 56,000 Btu/h | 208/230V, 1 phase, 60Hz | 39.1A | 45A | MDPHK06D / MDPHK09D / MDPHK12D |
Plain English: the 4- and 5-ton models share the same published MCA/MOP in the reviewed manual; that is a documented model relationship, not a tonnage assumption.
Source: Universal R-32 DC Inverter Package Unit Installation & Owner's Manual, pages 15, 16, 17, 18, 19.
| Capacity | Model | Cooling | Supply | MCA | MOP | Compatible auxiliary heat |
|---|---|---|---|---|---|---|
| 2 ton | MPH241H413B | 22,800 Btu/h | 208/230V, 1 phase, 60Hz | 15A | 20A | MHK05PB / MHK07PB / MHK10PB |
| 2.5 ton | MPH301H413B | 30,000 Btu/h | 208/230V, 1 phase, 60Hz | 18A | 25A | MHK05PB / MHK07PB / MHK10PB / MHK15PB |
| 3 ton | MPH361H413B | 34,200 Btu/h | 208/230V, 1 phase, 60Hz | 22.6A | 35A | MHK05PB / MHK07PB / MHK10PB / MHK15PB |
| 3.5 ton | MPH421H413B | 40,500 Btu/h | 208/230V, 1 phase, 60Hz | 24.2A | 35A | MHK05PB / MHK07PB / MHK10PB / MHK15PB / MHK20PB |
| 4 ton | MPH481H413B | 46,500 Btu/h | 208/230V, 1 phase, 60Hz | 26.8A | 40A | MHK05PB / MHK07PB / MHK10PB / MHK15PB / MHK20PB |
| 5 ton | MPH601H413B | 56,500 Btu/h | 208/230V, 1 phase, 60Hz | 34.9A | 55A | MHK05PB / MHK07PB / MHK10PB / MHK15PB / MHK20PB |
Source: VersaPro R-410A Packaged Heat Pump Specifications, pages 3, 4, 11.
| Capacity | Model | Cooling | Supply | MCA | MOP | Gas input / output |
|---|---|---|---|---|---|---|
| 2 ton | MPG24S060M413B | 24,000 Btu/h | 208/230V, 1 phase, 60Hz | 19A | 25A | 60,000 / 48,000 |
| 2.5 ton | MPG30S060M413B | 30,000 Btu/h | 208/230V, 1 phase, 60Hz | 21A | 30A | 60,000 / 48,000 |
| 3 ton | MPG36S090M413B | 36,000 Btu/h | 208/230V, 1 phase, 60Hz | 23A | 35A | 90,000 / 72,000 |
| 3.5 ton | MPG42S090M413B | 42,000 Btu/h | 208/230V, 1 phase, 60Hz | 28A | 40A | 90,000 / 72,000 |
| 4 ton | MPG48S090M413B | 48,000 Btu/h | 208/230V, 1 phase, 60Hz | 31A | 50A | 90,000 / 72,000 |
| 5 ton | MPG60S110M413B | 60,000 Btu/h | 208/230V, 1 phase, 60Hz | 37A | 60A | 110,000 / 88,000 |
Source: VersaPro R-410A Gas Package Unit Specifications, pages 3, 4.
Current storefront titles include Signature heat-pump models ending in ...M414A and gas/electric models ending in ...M414A. The available official specification sheets reviewed for this project use ...M414B heat-pump rows and ...M414A-2 gas/electric rows.
Governance sources: Signature Packaged Heat Pump Specifications, pages 2, 14; Signature Gas/Electric Packaged Unit Specifications, pages 2.
The base-unit table publishes the package equipment MCA and MOP.
The compatible heater adds its own published amperage, MCA, protection, stages, and separate-power instructions.
| Heat-kit model | kW | Heat stages | Amps | MCA | Max fuse/breaker |
|---|---|---|---|---|---|
| MHK05PB / MHK05PC | 3.8 / 5 | 1 | 18.1 / 20.8A | 23 / 26A | 25 / 30A |
| MHK07PB / MHK07PC | 5.6 / 7.5 | 1 | 27.1 / 31.3A | 34 / 40A | 35 / 40A |
| MHK10PB / MHK10PC | 7.5 / 10 | 1 | 36.1 / 41.7A | 46 / 53A | 50 / 60A |
| MHK15PB / MHK15PC | 11.3 / 15 | 2 | 54.2 / 62.5A | 68 / 79A | 70 / 80A |
| MHK20PB / MHK20PC | 15 / 20 | 2 | 72.3 / 83.4A | 91 / 105A | 100 / 110A |
What this means for you: a 5kW option has a much different electrical profile from a 20kW option. The 15kW and 20kW kits are two-stage in the source table. The source also instructs that the optional heater uses a separate power supply rather than being connected to the unit's single supply line. A two-stage heater is not automatically two heater branch circuits; follow the exact kit wiring diagram.
Sources: VersaPro R-454B Packaged Heat Pump Specifications, pages 3, 4, 6; VersaPro R-410A Packaged Heat Pump Specifications, pages 3, 4, 11; VersaPro R-410A Packaged Heat Pump Installation Manual, pages 27, 28, 29, 30.
Direct answer: it depends on the exact unit and installed heat configuration. The base package equipment has its published circuit requirements. In the reviewed VersaPro manual, a compatible electric heat kit uses a separate power supply from the base unit and has its own heater-circuit MCA and maximum protection.
A gas/electric unit does not use an electric resistance kit for its primary gas heat. A packaged heat pump without auxiliary electric heat does not have the same electrical picture as that same family with a large heater installed. Heat stages are not a substitute for counting documented supply circuits.
Takeaway: plan from the base-unit row only when no electric heater is installed.
Takeaway: base-unit and heater requirements remain separate planning facts.
Takeaway: gas provides heat, while the unit still needs its documented electrical circuit.
Line-voltage conductors supply the compressor, motors, controls, and any separately supplied compatible electric heater.
Reviewed package-heat-pump documentation identifies functions including R, C, Y, B, W/W1, and G. Gas/electric controls are documented for the exact packaged gas unit and thermostat application.
This is not a universal point-to-point terminal map. Terminal use, reversing-valve logic, staging, and auxiliary/gas heat calls differ by family and exact wiring diagram.
A supply voltage commonly encountered in certain building electrical systems.
The utilization-voltage rating used by the manufacturer for this equipment family.
Common field language for the residential supply class. Match the actual supply to the nameplate range; do not wire from casual wording alone.
Reviewed manuals call for a branch-circuit disconnect near, within sight of, and readily accessible to the unit, subject to applicable rules. They also direct the installer to use the unit rating-plate circuit ampacity and approved overcurrent protection.
“What does this exact package unit and installed heat option require?” Answered by the nameplates, MCA/MOP tables, wiring diagrams, and applicable code.
“Can the service and panel support this HVAC equipment plus everything else?” Answered by a proper load calculation across the home.
A large electric-heat option may matter to service planning. It does not automatically prove that a 200A service, panel replacement, or service upgrade is required.
Bad: “It is a 3-ton package unit.”
Good: “It is model MPH361HO13C with heat kit MHK15PC.”
The reviewed manuals call for a dedicated/independent equipment circuit and an accessible disconnect. Final design follows the exact model, nameplate, current manual, and applicable code.
There is no tonnage-only answer. The base unit has model-specific requirements, and the reviewed compatible VersaPro electric heater uses a separate heater supply with its own MCA and maximum protection.
Yes. Electricity operates the compressor, outdoor fan, blower, controls, ignition/safeties, and documented gas-section support equipment; gas supplies the primary heating energy.
Yes. The reviewed VersaPro heater table ranges from 5kW-class to 20kW-class options, with substantially different MCA and maximum protection values.
Yes. The reviewed VersaPro arrangement keeps the base-unit supply separate from the compatible heater supply. Do not assume the same arrangement across families; follow the exact wiring diagram.
Minimum Circuit Ampacity is the manufacturer-published starting point for the minimum conductor ampacity of that equipment or heater circuit.
It is the manufacturer-published maximum overcurrent-protection value. It does not replace the MCA or the final conductor/circuit design.
No. Models of similar capacity can have different MCA/MOP values, and heating type or auxiliary heat can change the electrical architecture.
That is the manufacturer's supported utilization-voltage range for these models. The measured supply and nameplate must be matched by the installer.
Yes. Resistance heat can be a major additional load. Use the exact compatible kit's nameplate, MCA/MOP data, and wiring instructions.
No. It may affect service planning, but only a complete load calculation can determine whether the panel or service needs work.
The exact unit and heat-kit nameplates, latest matching MRCOOL documents, applicable code, and the authority having jurisdiction control the installation.
Planning reference: specifications and available products can change. Verify the exact equipment nameplate and latest MRCOOL documentation before installation. Electrical and gas work must follow applicable requirements and be completed by the qualified professionals responsible for the installation.